Identification of Permanent Faults Based on Differential Current Protection for Transmission Lines with Two Shunt Reactors

SUONAN Jiale,SONG Guobing,SHAO Wenquan,SUN Dandan,ZHANG Yining(Xi'an Jiaotong University,Xi'an 710049,China)  
For transmission lines with two shunt reactors,this paper presents a novel method of identifying permanent faults for single-phase auto-reclosure.After the breakers of two terminals cut off the fault phase under the single-phase fault,the fault phase currents in the two terminals are compared based on the principle of differential current protection to judge whether the fault is permanent or temporary so as to determine whether to reclose the breakers of two terminals or not.Temporary faults can be regarded as external faults while permanent faults can be regarded as internal ones.ATP simulation results show that the method presented can identify permanent faults correctly and is hardly affected by grounding resistance.
【Fund】: 国家自然科学基金资助项目(50677051);; 高等学校博士学科点专项科研基金资助项目(20060698014)~~
【CateGory Index】: TM773