Experimental Research on Boiling Heat Trans- fer Characteristics of Smooth and Internally Ribbed Tubes in Vertical Water Walls in Subcritical and Near Critical Pressure Regions

Chen Ting-kuan, Bhen Xuan-zheng,Chen Xue-jun, Zhuang Wen-xian, Ding Hui-min, Xiao Guan-yao  
Experimental results concerning boiling heat transfer characteristics of steam-water two phase flow in σ22×5.5mm quadruply internally ribbed carbon steel tubes and σ18 × 3mm 1Cr18Ni9Ti smooth stainless steel tubes as used in sub critical and near critical pressure regions in domestic manufactured large once-through power boilers are presented. The tests were conducted in the electrically heated high pressure steam-water two phase flow test loop of the Xi'an Jiaotong University. The test parameters for internally ribbed tubes were as follows: pressure P=19.6-22.6MPa, rate of mass flow G = 650-l750kg/m2 ·s, heat flux accross the inner tube wall q=200-610kW/m2 ·s; and those for the smooth tubes were P=l7.2-22.6MPa, G=800-2000kg/m2·s, q = 240-630kW/m2. Via of wall temperature measurements within the range of test para-meters the criterion for boiling heat transfer deterioration and the effectiveness of deterring its occurrence in internally ribbed tubes were determined. Heat transfer characteristics of a few geometrically similar tubes are compared and evaluated.
Download(CAJ format) Download(PDF format)
CAJViewer7.0 supports all the CNKI file formats; AdobeReader only supports the PDF format.
【References】
Chinese Journal Full-text Database 2 Hits
1 Tang Bi guang (Wuhan,Wuhan University of Water Conservation and Power),Cai Jian guo,Xiang Jun,Liu Yong,Yu Yan zhi,Xue Wen yuan.;Experimental Study of the Origin of Transverse Cracks in Water Cooled Walls of Controlled Circulation Boilers[J];POWER EQUIPMENT;1997-05
2 Xiang Jun Liu Shengrong Tang Biguang Sun Xuexin;A Study of Boiler Water Wall Leakage and Boiler Expert System for Fault Diagnosis[J];JOURNAL OF HUAZHONG UNIVERSITY OF SCIENCE AND TECHNOLOGY;1999-09
【Citations】
Chinese Journal Full-text Database 1 Hits
1 Cheng Ting-kuan, Cheng Xuan-zheng, Zhao Jia-liang;Studies on the Two-Phase Flow Resistance Characteristics of Boiler Waterwall Bare Tubes and Internally Ribbed Tubes under Subcritical Pressure[J];Power Engineering;1987-04
【Co-citations】
Chinese Journal Full-text Database 3 Hits
1 Chen Ting-kuan, Chen Xuan-zheng, Chen Xue-jun, Zhao Jia-liang;Research on Frictional Pressure Drop of High Pressure Steam-Water Two-Phase Flow in Ribbed Tubes[J];Power Engineering;1989-03
2 Zheng Jian-xue(Xi'an Jiaotong University), Chen Ting-kuan, Luo Yu-shan,Bi Qin-cheng, Wu Lu-chen, Wang Xiao-wei, Liu Bao-sen, Chen Chun-da;Investigation on The Characteristics of internally Riffled Tubes TwoPhase Flow Friction Pressure Losses in Subcritical and Near Critical Pressure Region[J];POWER ENGINEERING;1995-01
3 Zheng Jianxue;Chen Tingkuan;Luo Yushan;Bi Qincheng(Xi'an Jiantong University)Wu Luchen;Wang Xiaowei;Liu Baosen;Chen Chunda(Harbin Boiler Works);INVESTIGATION ON THE CHARACTERISTICS OF HIGH PRESSURE STEAM-WATER TWO-PHASE FLOW FRICTION PRESSURE LOSS IN RIFLED TUBES[J];JOURNAL OF XI'AN JIAOTONG UNIVERSITY;1994-05
【Co-references】
Chinese Journal Full-text Database 4 Hits
1 Liu Wei (Shanghai, Shanghai Power Equipment Research Institute), Cai Shi-ling;Zhu Cai-guang.;Experimental Study of Heat Transfer of Steam-Water Mixtures, Flowing under Sub-Critical Pressure in Φ60mm × 7mm TubesRifled with Rectangular Grooves.[J];POWER ENGINEERING;1996-04
2 Tang Bi guang (Wuhan,Wuhan University of Water Conservation and Power),Cai Jian guo,Xiang Jun,Liu Yong,Yu Yan zhi,Xue Wen yuan.;Experimental Study of the Origin of Transverse Cracks in Water Cooled Walls of Controlled Circulation Boilers[J];POWER EQUIPMENT;1997-05
3 Zhang Jianxie;Analysis and Prospect on Boiler Tube Failure Within ECPN in 1995[J];EAST CHINA ELECTRIC POWER;1996-07
4 Yan Mingyin Shi Tielin Wang Xue Yang Shuzi;On the Uncertainty in Diagnostic Knowledge Acquisition[J];;1993-01
【Secondary References】
Chinese Journal Full-text Database 1 Hits
1 Xiang Jun Liu Shengrong Tang Biguang Sun Xuexin;A Study of Boiler Water Wall Leakage and Boiler Expert System for Fault Diagnosis[J];JOURNAL OF HUAZHONG UNIVERSITY OF SCIENCE AND TECHNOLOGY;1999-09
【Secondary Citations】
Chinese Journal Full-text Database 1 Hits
1 Xiong Da-ji;Flow Characteristics of the Two Phase Water and Steam Flow within a Quadruple-lead Ribbed Tube[J];Power Engineering;1983-06
©2006 Tsinghua Tongfang Knowledge Network Technology Co., Ltd.(Beijing)(TTKN) All rights reserved