Investigation on Hydrogen Inerting Mechanism of Enviromental-friendly Freon Under Severe Accident in Nuclear Power Plant

ZHANG Sheng-jun;SHEN Feng;State Nuclear Power Research Institute;  
In dealing with the hydrogen risk management under severe accident,the study of the minimum inerting concentration(MIC)on hydrogen of different gases was carried out.And the mechanism difference between conventional inert gas and freon was elaborated.The inhibition factor of inert gas was calculated by the group contribution method.The MIC was predicted with flame propagation speed and stoichiometric concentration.The results show that the MICs of HFC-134 a,HFC-245 fa and HFC-125are15.87%,14.12% and 10.39%,respectively.HFC-125 shows the best inerting performance.The minimum inhibition concentrations of the three freon are 34.9%,32.7%and 25.9%,which are much lower than N2 and CO2with 94.5%and 90.9%.
【CateGory Index】: TL364.4
Download(CAJ format) Download(PDF format)
CAJViewer7.0 supports all the CNKI file formats; AdobeReader only supports the PDF format.
【Citations】
Chinese Journal Full-text Database 2 Hits
1 LIU Huan-Wei YANG Zhao ZHANG Kui (Thermal Energy Research Institute,Tianjin University,Tianjin 300072,China);Theoretical and Experimental Research on the Inert Effect of Flammable Refrigerants[J];工程热物理学报;2011-08
2 YANG Zhao, LI Li xin, TIAN Guan san, MA Yi tai(Heat Energy Institute,Tianjin University,Tianjin 300072,China);Theoretical and Experimental Research of the Explosive Properties about Alternative Mixtures[J];燃烧科学与技术;2002-02
【Co-citations】
Chinese Journal Full-text Database 7 Hits
1 ZHANG Sheng-jun;SHEN Feng;State Nuclear Power Research Institute;;Investigation on Hydrogen Inerting Mechanism of Enviromental-friendly Freon Under Severe Accident in Nuclear Power Plant[J];原子能科学技术;2014-S1
2 WU Xi;YANG Zhao;SHI Yong-Zheng;Thermal Energy Research Institute,Tianjin University;Key Lab of Heating,Gas Supply,Ventilating and Air Conditioning Engineering,Beijing University of Civil Engineering and Architecture;;Assessment on Refrigerant Charge Limitation Basing on a Comprehensive Consideration of Combustion Characteristics[J];工程热物理学报;2013-11
3 Ni Hao(Johnson Controls Building Efficiency Technology(Wuxi) Co.,Ltd.);Performance studies on R134a/R600a refrigerants applied to large scale air source heat pump[J];制冷与空调;2010-02
4 CHEN Jian-Xin HU Peng CHEN Ze-Shao JIANG Bin (Dept.of Thermal Science and Energy Engineering,University of Science and Technology of China,Hefei 230027,China);THERMODYNAMIC PROPERTIES OF R125/R600a BINARY MIXTURE[J];工程热物理学报;2008-04
5 YANG Zhao PENG Ji-jun HUANG Hai-tao(Thermal Energy Research Institute,Tianjin University,Tianjin 300072,China);Theoretical and Experimental Study on Flame-Retarding Characteristics of R245fa[J];燃烧科学与技术;2006-04
6 YANG Zhao, JIN Guo-min, ZHANG Shi-gang (Thermal Energy Research Institute, Tianjin University, Tianjin 300072, China);Theoretical Study on the Mixtures Containing R290 as Refrigerants for Domestic Air-conditioners[J];制冷空调与电力机械;2005-01
7 By Hu Peng, Zhao Tao and Chen ZeshaoUniversity of Science and Technology of China, China;Theoretical Refrigeration Cycle Analysis of HFC125/HCs Binary Mixtures[J];制冷学报;2004-02
©2006 Tsinghua Tongfang Knowledge Network Technology Co., Ltd.(Beijing)(TTKN) All rights reserved