TREATMENT OF LINES WITH MUTUAL INDUCTANCE IN POWER SYSTEM FAULT CALCULATION

SHI Dong-yuan, LI Yin-hong, DUAN Xian-zhong, HE Yang-zan (Department of Electrical Power Engineering, Huazhong University of Science and Technology, Wuhan 430074, China)  
In the power system fault calculation method based on node admittance matrix Y, the construction of Y is complicated because of the existence of lines with mutual inductance, especially when there are faults on them. This paper presents a simple algorithm to treat multiple mutual lines as well as segmental mutual lines based on mathematical analysis. And a universal rule as the guidance in the separation of segmental mutual lines under fault condition is proposed. The algorithm and rule presented make the fault calculation method flexible enough to meet the requirements of large power system with multiple mutual lines, multiple segmental mutual lines, and multiple faults on mutual lines. And the practicability of fault calculation software can be greatly promoted.
【Fund】: 教育部高等学校优秀青年教师教育与科研基金项目。
【CateGory Index】: TM711