Research on Methods to Improve the Response Time of Magnetically Controlled Shunt Reactor

XING Kezheng;State Grid DC Construction Corporation;  
The main circuit and working principle of high capacity Extra-High Voltage magnetically controlled shunt reactor were introduced.The main problem which response time was too long of its application in the Super/UHV power system was analyzed.Three effective solutions were proposed to this problem:increasing the DC control voltage,making use of the discharge of charging capacitor,adopting the DC magnetic pre-bias.The main advantages and disadvantages of the three methods in practical applications were compared and analyzed.The effectiveness of the proposed methods was verified through theoretical analysis and simulation results.