Analysis of Continuous Increase in Output Current of Desulphurization 110VDC Charger

HUANG Muqing;Guangdong Zhuhai Power Station;  
The desulphurization 110 V DC charger continues to have abnormal large current output and several charging modules failed.It was considered that the most fundamental reason was the deep discharge of the battery.The improvement measures were proposed to ensure the safe operation of the unit.
【CateGory Index】: TM912