Full-Text Search:
Home|Journal Papers|About CNKI|User Service|FAQ|Contact Us|中文
《Energy Conservation Technology》 2009-03
Add to Favorite Get Latest Update

Identification Research for Rheological Characteristic of Working Fluid in Sewage Heat Pump

XU Ying,ZHANG Cheng-hu,SUN De-xing (School of Municipal & Environmental Engineering,Harbin Institute of Technology,Harbin 150090,China)  
Urban sewage is a kind of excellent and reproducible heat source whose low-temperature waste is available.Sewage source heat pump,which is of energy-saving and environmental protection significance,can make best use of the exhaust heat in urban sewage for heating and cooling.Rheological characteristic of the urban sewage is an important basis of thermal and flowing calculation.In this paper,the relation of shear strain rate with shear stress of the urban sewage is determined based on experiments. Constitutive equation of the working fluid is confirmed by system identification method.Results indicate the sewage source heat pump's working fluid shows the characteristics of non-Newtonian fluid,and belongs to yield-pseudoplastic fluid.
【Fund】: 建设部研究开发项目(2008-K1-23);; 北京市“供热供燃气通风及空调工程”重点试验室开放课题(KF200710)资助项目
【CateGory Index】: TU831.6