Fire safety design for a large commercial plaza reconstruction project

SHEN Yi-hui;Dongguan Fire Detachment;  
The problems of the fire safety design for a large-scale commercial plaza renovation project were analyzed,including that the fire compartment is too large,and the safety evacuation can't satisfy related standards.Against these problems,adjustments were put forward,including setting fire separation,using 1.00hfire-resistant components on both sides of the pedestrian street,and adding 10 escape stairs and using class A fire door to adjacent fire compartment or indoor pedestrian street as auxiliary exits.The safety analysis was conducted to these plans.Results showed that,the fire safety measures can satisfy the requirement of evacuation,and help with the firefighting.
【CateGory Index】: TU247;TU892